Technical description
Range | -50…70 °C |
Protection class | IP54, cable or probe downwards |
Cable gland | M16 |
Mounting | with flange, adjustable < 200 mm |
Materials | PBT, PC, PA, stainless steel |
TEK sensors are designed for detecting temperatures inside ventilation ducts.
Range | -50…70 °C |
Protection class | IP54, cable or probe downwards |
Cable gland | M16 |
Mounting | with flange, adjustable < 200 mm |
Materials | PBT, PC, PA, stainless steel |
TYPE | ARTICLE | DESCRIPTION |
TEK PT 100 | 1173040 | 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, EN 60751/B |
TEK PT 1000 | 1174040 | 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent) |
TEK NTC 1.8 | 117E040 | 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (TAC equivalent) |
TEK NTC 2.2 | 1172040 | 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent) |
TEK NTC 10 | 1175040 | 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Trend equivalent) |
TEK NTC 10-AN | 117H040 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent) |
TEK NTC 10-C | 117M040 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent) |
TEK NTC 10-KB | 117B130 | 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent) |
TEK NTC 20 | 1176040 | 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent) |
TEK NI 1000 | 117C040 | 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent) |
TEK NI 1000-LG | 1178040 | 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent) |
TEK KP 10 | 117J040 | LM235Z, 10 mV/K, 2,98 V / 25 °C |
TEK T1 | 117V040 | 2226 Ω / 0 °C, accuracy ±0,4 °C / 0 °C |
TEK LL | 1177040 | 2-wire transmitter/controller, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C |
TEK LU | 1179040 | 3-wire transmitter/controller, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C |
TEK-M | 117Z040 | Modbus transmitter/controller, supply 24 Vac/dc, accuracy ±0,5 °C |
TE-N V2 | 1170250 | display option for the transmitters |
ML-SER | 1139010 | transmitter commissioning tool |