HDU – Carbon Dioxide (CO₂) transmitters
HDU transmitters are designed for detecting CO₂ concentration and temperature in underground parking garages and parking halls. ABCLogic™ self-calibration method eliminates the possible long term drift.
Technical description
Supply |
24 Vac/dc, < 10 VA |
Range |
(CO₂) 0…2000 ppm |
Range (temperature) |
-50…50 °C |
Accuracy (CO₂) |
typ. ±40 ppm ±3 % of value |
Accuracy (temperature) |
±0,5 °C |
Output |
3 x 0…10 Vdc, 2 mA |
Protection class |
IP54, cable downwards |
Ambient temperature |
-30…50 °C |
Humidity |
0…85 %rH |
Cable gland |
M16 |
Mounting |
with screws, external lugs |
Dimensions |
105 x 110 x 46 mm |
Product range
TYPE |
ARTICLE |
DESCRIPTION |
HDU |
1135090 |
CO₂ transmitter for cold spaces |
HDU-N |
1135091 |
CO₂ transmitter with display |
HDU-M |
1135150 |
Modbus CO₂ transmitter for cold spaces |
HDU-M-N |
1135151 |
Modbus CO₂ transmitter with display |
HDU-5K |
1135160 |
CO₂ transmitter for cold spaces, range 0…5000 ppm |
HDU-5K-N |
1135161 |
CO₂ transmitter with display, range 0…5000 ppm |
HDU-5K-M |
1135170 |
Modbus CO₂ transmitter for cold spaces, range 0…5000 ppm |
HDU-5K-M-N |
1135171 |
Modbus CO₂ transmitter with display, range 0…5000 ppm |
ML-SER |
1139010 |
transmitter commissioning tool |
Options
HD-R |
1135003 |
relay, 24 Vac 1 A |