TEL – cable temperature sensors, floor installation

TEL sensors are designed for detecting floor temperatures. The sensor is installed in the cable duct inside the floor construction.

Technical description

 

Range -30…80 °C
Sensor Ø 7 mm
Cable 3 m (LIYY 2 x 0,5), PVC, other lengths also available

 

Product range

TEL PT 100 1173280 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, EN 60751/B
TEL PT 1000 1174280 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEL NTC 1.8 117E280 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (TAC equivalent)
TEL NTC 2.2 1172280 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEL NTC 10-AN 117H280 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEL NTC 10-C 117M280 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEL NI 1000 117C280 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEL NI 1000-LG 1178280 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)