Technical description
Range | 0…50 °C |
Protection class | IP20 |
Material | ABS plastic |
Ambient temperature | 0…50°C |
Mounting |
with screws on wall or on a junction box (hole distance 60 mm) |
Dimensions |
86 x 86 x 32 mm |
TEHR-P sensors are designed for detecting room temperatures and adjusting the temperature set point. The potentiometer value and the fitting resistor values can be defined in the order.
Range | 0…50 °C |
Protection class | IP20 |
Material | ABS plastic |
Ambient temperature | 0…50°C |
Mounting |
with screws on wall or on a junction box (hole distance 60 mm) |
Dimensions |
86 x 86 x 32 mm |
TYPE | ARTICLE | DESCRIPTION |
TEHR PT 100-P | 1173230 | 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, EN 60751/B |
TEHR PT 1000-P | 1174230 | 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent) |
TEHR NTC 1.8-P | ‘117E230 | 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (TAC equivalent) |
TEHR NTC 2.2-P | 1172230 | 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent) |
TEHR NTC 10-AN-P | 117H230 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent) |
TEHR NTC 10-C-P | 117M230 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent) |
TEHR NTC 10-P | 1175230 | 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Trend equivalent) |
TEHR NTC 20-P | 1176230 | 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent) |
TEHR NI 1000-LG-P | 1178230 | 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent) |
TEHR NI 1000-P | 117C230 | 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent) |
TEHR KP 10-P | 117J230 | LM235Z, 10 mV/K, 2,98 V / 25 °C |
TYPE | ARTICLE | DESCRIPTION |
TEHR-K5 | 1170240 | 5-position rotary switch (1, 2 ,3, 0, A) 24 Vac/dc |
TEHR-L | 1170100 | LED 24 V |
TEHR-S | 1170080 | push button (no / nc) 24 Vac/dc |
TEHR-N | 1170140 | digital display, input 0…10 V = 0…50 °C |