Technical description
Accuracy (at applied pressure):
At low limit (Typical):
PS200: ± 5 Pa
PS300: ± 5 Pa
PS500: ± 5 Pa
PS600: ± 5 Pa
PS1500: ± 10 Pa
PS4500: ± 50 Pa
Overpressure:
Proof pressure: 25 kPa
Burst pressure: 50 kPa
Media compatibility:
Dry air or non-aggressive gases
Measuring units:
Pa
Measurement range:
PS200: 20-200 Pa
PS300: 30-300 Pa
PS500: 30-500 Pa
PS600: 40-600 Pa
PS1500: 100-1500 Pa
PS4500: 500-4500 Pa
Environment:
Operating temperature: -20…60 °C
Storage temperature: -20…85 °C
Humidity: 0 to 95 % rH, non condensing
Dimensions:
Case: 105 x 73 x 63 mm
Weight:
150 g
Mounting:
2 each 4.3 mm screw holes, one slotted
Materials:
Case: ABS
Cover: PC
Membrane: Silicone
Duct connectors: ABS
Tubing: PVC
Protection standard:
IP54
Electrical connections:
3 screw terminals
Wire: 12–24 AWG (0.2–1.5 mm2)
Cable entry:
Strain relief: M16
Knockout: 16 mm
Pressure fittings:
Male Ø 5.0 mm
Input:
24–250 VAC
Output:
NO / NC circuit
Switching differential:
PS200: 20 Pa
PS300: 20 Pa
PS500: 20 Pa
PS600: 30 Pa
PS1500: 80 Pa
PS4500: 250 Pa
Conformance:
Meets requirements for CE marking:
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
Low voltage 73/32/EEC