Technical description
Range | -50…120 °C |
Time constant | 2,5 s |
Cable | 2 m, LIYY 2×0,14 |
Connection | R ¼” |
Materials | acid proof steel, brass |
Mounting depth | < 200 mm (also available < 400 mm) |
Pressure rating | PN16 |
TEV sensors are designed for frost protection and for applications with fast response.
Range | -50…120 °C |
Time constant | 2,5 s |
Cable | 2 m, LIYY 2×0,14 |
Connection | R ¼” |
Materials | acid proof steel, brass |
Mounting depth | < 200 mm (also available < 400 mm) |
Pressure rating | PN16 |
TYPE | ARTICLE | DESCRIPTION |
TEV PT 100 | 1173020 | 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, EN 60751/B |
TEV PT 1000 | 1174020 | 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent) |
TEV NTC 1.8 | 117E020 | 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (TAC equivalent) |
TEV NTC 2.2 | 1172020 | 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent) |
TEV NTC 10 | 1175020 | 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Trend equivalent) |
TEV NTC 10-AN | 117H020 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent) |
TEV NTC 10-C | 117M020 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent) |
TEV NTC 10-KB | 117B020 | 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent) |
TEV NTC 20 | 1176020 | 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent) |
TEV NI 1000 | 117C020 | 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent) |
TEV NI 1000-LG | 1178020 | 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent) |
TEV LL | 1177020 | 2-wire transmitter/controller, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C |
TEV LU | 1179020 | 3-wire transmitter/controller, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C |
TEU-N V2 | 1170270 | display option for TEU LL and TEU LU transmitters |
ML-SER | 1139010 | transmitter commissioning tool |