Technical description
Range | -50…70 °C |
Protection class | IP54, cable or probe downwards |
Length | 500 mm |
Cable gland | M16 |
Mounting | With flange |
Materials | PBT, PC, PA, stainless steel |
TEKA-500 sensors are designed for detecting temperatures inside ventilation ducts. Sensor detects the average temperature with 4 sensor elements.
Range | -50…70 °C |
Protection class | IP54, cable or probe downwards |
Length | 500 mm |
Cable gland | M16 |
Mounting | With flange |
Materials | PBT, PC, PA, stainless steel |
TYPE | ARTICLE | DESCRIPTION |
TEKA PT 100-500 | 1173170 | 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, EN 60751/B |
TEKA PT 1000-500 | 1174170 | 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent) |
TEKA NTC 1.8-500 | 117E170 | 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (TAC equivalent) |
TEKA NTC 2.2-500 | 1172170 | 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent) |
TEKA NTC 10-500 | 1175170 | 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Trend equivalent) |
TEKA NTC 10-AN-500 | 117H170 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent) |
TEKA NTC 10-C-500 | 117M170 | 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent) |
TEKA NTC 10-KB-500 | 117B170 | 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent) |
TEKA NTC 20-500 | 1176170 | 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent) |
TEKA NI 1000-500 | 117C170 | 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent) |
TEKA NI 1000-LG-500 | 1178170 | 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent) |
TEKA LL-500 | 1177170 | 2-wire transmitter/controller, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C |
TEKA LU-500 | 1179170 | 3-wire transmitter/controller, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C |
TEKA-M-500 | 117Z170 | Modbus transmitter/controller, supply 24 Vac/dc, accuracy ±0,5 °C |
TE-N V2 | 1170250 | display option for the transmitters |
ML-SER | 1139010 | transmitter commissioning tool |