Technical description
Supply |
200…415 V AC, 50…60 Hz, 1- or 2-phase, automatic adaption |
Ambient temperature |
Max. 30°C (Note: Pulser generates 20 W at maximum heating) |
P-band |
20 K (rapid temperature changes)1,5 K (slow temperature changes) |
I-time |
6 min (rapid temperature changes) |
Pulse period |
60 s |
Inputs/outputs (I/Os) |
|
Sensor |
One main sensor or two main sensors (only PULSER-M) |
Setpoint |
0…30°C (Sensor determines the range (Regin NTC sensor)) |
Night setback |
0…10 K |
Output (load) |
16 A (min. 1 A) 1-phase max. 3.6 kW, 2-phase max. 6.4 kW |
With automatic adaption 230 V AC or 400 V AC
Description |
Mounting |
Protection class |
Type |
Electric heating controller |
Wall |
IP30 |
PULSER |
Electric heating controller |
DIN-rail, 6.6 modules(115 x 88 x 59) |
IP20 |
PULSER/D |
Add-on unit |
Wall |
IP30 |
PULSER-ADD |
Electric heating controller with min./max. limitation |
Wall |
IP30 |
PULSER-M |
Electric heating controller for external 0…10 V DC control signal |
DIN-rail, 6.6 modules(115 x 88 x 59) |
IP30 |
PULSER-X/D |
1-phase (230 V AC) or 2-phase (400 V AC)
Description |
Supply voltage |
Mounting |
Type |
Electric heating controller forexternal 0…10 V DC control signals |
230 V AC |
Wall |
PULSER220X010 |
400 V AC |
Wall |
PULSER380X010 |
PULSER-X/D Declration of Conformity
Pulser XD Declaration of Conformity